Bioxide® Solution Reduces Odors, Corrosion, and Complaints

Mid-Atlantic Water Authority replaces a liquid bleach system with a nonhazardous solution for effective odor and corrosion control

Challenge

Evoqua Water Technologies was contacted by a Mid-Atlantic Water Authority to propose an odor control solution at one of their pump stations. The Authority was treating the odors with a sodium hypochlorite (bleach) solution to varying degrees of success. Downstream hydrogen sulfide levels in the atmosphere were the primary contributors to odor complaints, reports of corrosion, and worker safety issues. Evoqua had provided other odor control solutions at a different location for the Authority previously, but this site was still using a legacy solution.

The customer also had chlorine nuisance odors at the bleach dose site. This caused pump station component corrosion, worker complaints and irritation, so a non-hazardous solution was preferred. Background data collected with bleach dosing at a rate of 1,200 gpd showed a treated level of dissolved sulfide of 1.5 mg/l and an average of above 40 ppm of atmospheric hydrogen sulfide at the control point.​

 

Solution

Evoqua evaluated the situation and determined that BIOXIDE®​ Calcium Nitrate Solution was the best treatment method. Bioxide solution contains no hazardous substances and is a safe, easy-to-handle method of odor control. It also reduces future corrosion by effectively eliminating dissolved hydrogen sulfide.

The Mid-Atlantic water authority was a little apprehensive about using a non-chemical product. As a result, Evoqua offered to provide on-site testing to evaluate performance.​

Evoqua provided complete, turnkey services with safety trained personnel, working with the customer to empty the existing bleach tanks, safely clean them out, and install a new dosing controller. The Mid-Atlantic water authority utilized our full service odor control program, consisting of BIOXIDE Solution​​​, VersaDose® LT dosing controller, and VaporLink® online atmospheric hydrogen sulfide monitors. The system provides remote monitoring and dosing control with 24 hour, 7 day set points to optimally treat varying hydrogen sulfide levels.

The VersaDose LT dosing controller provides 24/7 customized dosing control.

Results

Evoqua worked closely with the customer to determine dosing rates and profiles for optimal odor control. Final summertime feed rates were roughly 400 gpd, with a < 2 ppm average atmospheric hydrogen sulfide at the control point.

After reviewing the final results and feed rates, the customer elected to continue with Bioxide solution. Evoqua quickly provided the customer with a working system and met their goals of reducing hydrogen sulfide odors and nuisance chlorine gas issues​.​

靠谱权威风云体育_官方网站-IOS/Android通用版/手机APP下载/最新版 半岛十大真人网_官方网站-IOS/Android通用版/手机APP下载/最新版 E体育十大正规足球_官方网站-IOS/Android通用版/手机APP下载/最新版 风云权威体育充值_官方网站-IOS/Android通用版/手机APP下载/最新版 多福多财怎么玩_官方网站-IOS/Android通用版/手机APP下载/最新版 江南权威最火网_官方网站-IOS/Android通用版/手机APP下载/最新版 知名最新和记体育直营_官方网站-IOS/Android通用版/手机APP下载/最新版 和记体育网络正规网站_官方网站-IOS/Android通用版/手机APP下载/最新版 和记体育信誉知名网站_官方网站-IOS/Android通用版/手机APP下载/最新版 B体育网上最大足球_官方网站-IOS/Android通用版/手机APP下载/最新版